Description
R59 Series Circuit Breaker Fuse Holder Type
Electrical Characteristics (@ 25°C)
Calibration: Will continuously carry 100% of rating.
0.25 to 2 Amp types: May trip between 101% and 174%,
Must trip at 175% of rating within one hour at +25°C
3.0 to 20 Amp types: May trip between 101% and 134%,
Must trip at 135% of rating within one hour at +25°C
Maximum Operating Voltages: 32 VDC; 250 VAC, @ 50/60 Hz
Dielectric Strength: 1500VAC RMS
Resettable Overload Capacity:
0.25 to 2 Amp types: Six times rated current
3.0 to 20 Amp types: Ten times rated current
Reset Time:
0.25 to 2 Amp types: 180 seconds max.
3.0 to 20 Amp types: 10 to 60 seconds typ.
Interrupt Capacity: 1000 Amps @ 250 VAC, 50/60 Hz. and 32 VDC
in accordance with UL standard 1077
Mechanical Characteristics
Termination: .250 (6.35) Quick Connect Terminals
NOTE: Soldering to terminals is not recommended.
Mounting: Snaps into panel from front
(See Recommended Panel Cutouts)
Features
- Replaces Slow Blow Glass Cartridge Fuse
- .250” (6.35mm) Quick Connect Terminals
- Snap−In Mounting
- Visual Trip Indicator
- Push Button to Reset Breaker
Link to Spec Sheet